Common errors of FUJI Inverter
Continuing the series of common errors on Fuji Electric , Hao Phuong would like to send to customers a solution to overcome engine overload, inverter overload, memory errors and communication errors at Fuji Electric inverter
1. OL 1 – Motor Overload
Possible causes |
checking & fixing |
|
1 |
Engine temperature exceeds the permitted level. |
Check engine value. Change function parameters F10 and F12. |
2 |
Motor protection parameters are not suitable. |
Continue to check the engine’s permissible line. Change parameters of function F11. |
3 |
Load too heavy |
Check the output line. Changing parameters depends on the load |
2. OLU – Inverter Overload
Possible causes |
checking & fixing |
|
1 |
Engine temperature exceeds the permitted level. |
Check the room temperature. Cooling the inverter. |
2 |
Load too heavy |
Check the output line. Define the parameters of the F26 function. |
3 |
Ventilation door is blocked. |
Check and clean. Check the inverter cooling fan |
4 |
The working time of the cooling fan is prolonged or due to the fan life. |
checking the fan, replace if necessary |
3. Er 1 – Memory error
Possible causes |
checking & fixing |
|
1 |
While the drive is recording data (especially if it is installing or copying data), power is lost or voltage drop. |
Testing by pressing the RESET key can be reset and then the control code is reset by reinstalling the H03 function code to 1. Return to the original installation function code and start the installation again. |
2 |
Large noise signals are caused to the Inverter when It records data. |
Check the installation of inverter in accordance with the working environment conditions, can be checked as (1). |
3 |
The control circuit is faulty. |
Reinstall the function code by setting the H03 function to 1, reset the fault by pressing the RESET key. |
4. Er 2 – Keypad communication
Possible causes |
checking & fixing |
|
1 |
The cable is broken or there is a connection problem. |
Check the cable. Cable ends and contacts. Replace the cable |
2 |
Large noise signal caused to the drive. |
Check the installation of the inverter in accordance with the working environment conditions. Take appropriate anti-noise solutions |
3 |
The keyboard has a problem |
Try changing the other keyboard for the drive to see if it still gives an error. If it does not report an Er2 error , the keyboard was fail. |
Hao Phuong specializes in distributing genuine electrical and industrial equipment from reputable manufacturers in the region and the world. Contact Hotline 1800 6547 to get more information about the product as well as Hao Phuong’s policy.