Common errors of FUJI Inverter and How to fix them – Part II

Common errors of FUJI Inverter

Following part 1, in this part, Hao Phuong would like to send to customers how to fix the error of overheating protection error, internal overheating fault, external fault on Fuji Electric inverter.

  1.  OH1 – Cooling fan overheat 

Possible causes

Checking and Fixing

1

The temperature of the inverter exceeds the allowed temperature

Check the temperature around the inverter

2

Ventilation door is blocked

Clean the inverter
Check if the cooler is blocked

3

The working time of the cooling fan exceeds the normal level, or the cooling fan fails

Check the fan working time.
Replace fan.
Visual inspection whether the rotary fan is abnormal or not

4

Load too heavy

Check the output line.

 

  1. OH2 – External alarm 

Possible causes

Checking and Fixing

1

Error function of external device

Check if the external device is working.
Removing any device causes an error

2

Connection errors

Check if the fault line is correctly connected to the terminal (External failure) (E01-08, E98, E99 set to 9)

3

Wrong settings

Resetting.

 

  1. OH3 – Inverter inside overheat 

Possible causes

Checking and Fixing

1

The ambient temperature exceeds the allowable limit of the inverter

Check the ambient temperature
Improve the ambient temperature by improving the inverter cooling system

 

  1. OH4 – Motor protection

Possible causes

Checking and Fixing

1

The temperature around the motor exceeds the allowed temperature of the engine

Check the temperature around the engine

2

Cooling fan system failed

Check cooling and repair system if damaged.

 