Common errors of Fuji Electric inverter and How to fix them
In Part 5, we learned about the connection errors and hardware errors. Continuing the series of common errors on Fuji Electric Inverter in this part, Hao Phuong would like to send to customers the solutions to fix the communication error (CAN bus), error of speed control and error related to the charging source.
-
Erb – CAN bus comunications error
Possible causes |
How to check and fix |
|
1 |
Due to Error in actuator |
Checking for the connection between the drive (Y24) and Host. Adjust it properly. |
2 |
Due to Hardware failure of Host, operating system or configuration |
Checking for the Host |
3 |
Due to Connection loss or unstable connection of cable |
Checking for the cable Replacing the cable |
4 |
Due to large noise signal caused to inverter |
Checking for the installation of inverters in accordance with working environment conditions. |
-
OS – Over speed error
Possible causes |
How to check and fix |
|
1 |
Engine configuration error |
Checking for the correlation when installing P01 and L02 |
2 |
Due to large noise signal caused to inverter |
Check installation of inverters in accordance with working environment conditions. |
3 |
due to external controller has been used |
Checking for the cable, the external speed controller noise. Using anti-noise cable or twisted-pair cable for control signal connection. Checking for the noise from the inverter if it affect the noise for the motor speed. |
-
ErE – Out of control speed
Possible causes |
How to check and fix |
|
1 |
Configuration error |
Checking for the L90, L91, L92 function installation. |
2 |
Due to overload |
propose solutions for output currents |
3 |
Due to Output speed cannot be increased by the current limit |
Checking for F44 |
4 |
Engine parameters error |
Checking for the settings of P01, P02, P03, P06, P07, P09, P10 and P12 function to match the engine. |
5 |
Connection error of encoder |
Checking for the wire. |
6 |
The connection to the motor is incorrect. |
Checking for the wire to the motor. |
7 |
The Amplification of the speed controller is too large or too small |
Reconfigure L36, L39 |
-
OE – Over torque error
Possible causes |
How to check and fix |
|
1 |
Output of inverter is lost |
Checking for the connection of inverter output (U, V, W) to the motor. |
2 |
The connection between the encoder and option card is broken |
Checking connection |
3 |
Too heavy Loading |
Measuring the current of the motor and record. Checking if it is suitable for the design. If it is too heavy, replace the higher frequency inverter. |
4 |
due to Time to accelerate and decelerate too fast |
Checking if the motor moment is responsive during acceleration or deceleration. |
5 |
Wrong motor settings |
Checking for the engine parameters (P function) |
6 |
The motor’s polarity is wrong |
Change the number of poles |
-
PbF – Charger circuit fault
Possible causes |
How to check and fix |
|
1 |
There is no source of magnetic start, short-circuit resistance load. |
Check the input source by inserting a 1-phase power into 2 pins R0 and T. |
Hao Phuong specializes in distributing genuine electrical and industrial equipment from reputable manufacturers in the region and the world. Contact Hotline 1800 6547 to get more information about the product as well as Hao Phuong’s policy.